sdg.matiaan
2019-07-01 12:58
Last Edited 2022-08-18 17:07
You can download software to read the Wasion DTSY341-5V3.3G (3 Phase integrated keypad with GPRS) IEC meter here (120k)
Latest Version: 2019-07-01
*added error codes
sdg.corrie
2019-09-16 08:45
Get the server IP address that will be used to
log the meter data from the Client. Or Adam (''196.22.139.148'')
SMS the AT set-up commands below to the modem:
1: First send
                                    #AT+APN=internet,user,pass
(most service
providers only want something in the user and Password field)
(When using
your own APN fill in the details as specified for your APN)
                                    2:
Then send
                                    #AT+APN?          See if what you sent matches the reply
sms
                                    3:
Then send
                                    #AT+GPRS=0,''server IP address'',2230  Note: That the IP must be between '' ''
                                    4:
Then send
                                    #AT+GPRS?
      See if what you sent matches the reply
sms
                                    5:
Then send
                                    #AT+HBTT=300
                                    6:
Then send
                                    #AT+HBTT?
The reply will be (+HBTT:300 OK) 
                                    7:
Then send
                                    #AT+CSQ
                                    The
reply is the signal strength. Note:
17-31 is usable connection 31=100%
                                    Improve