Why does my Kamstrup standalone meter not call in?

Avatar

sdg.marinusvz
2026-08-04 14:29

Transcribed from a support Whatsapp

It works on OmniPower and on M2M Portal and on Scigrow. It is only on PnP that it doesn't read


Avatar

sdg.marinusvz
2026-08-04 14:33

It is weird, because we read many KMP Kamstrup meters for other clients. Last month we read 10011 KMP meters. 

I see that there is a conversation happening on pnpscada when you try to read the meter?

I see from your comms log that you sent from OmniPower that you use multidrop 9.


On PNPSCADA, it uses 3F, which is broadcast. The reason is because you have only one KMP meter added on the modem.

How many meters did you physically multidrop on that modem? According to your pnpscada configuration there is only one, but I suspect that is false, that you actually install more meters on there, because you are mixing systems....

Anyhow, I've added a KMP meter on that meter, with a fictional serial and multidrop, and which I disabled.

Now we are using the specified multidrop ID in the protocol, which is a second byte of 9. And it seems to be calling in now.



Please log in to post a comment